[5-2 Outdoor Unit Control ]
- 140 -
HWE1314A
GB
(2) Defrost operation
* When PWFY-AU model units are connected, SVA and SVC on the BC should be set to ON.
* Outdoor air temperature (TH7) < -10°C and SVA and SVB are ON when PWFY-AU is not connected
(3) Stopping the defrost operation
The defrost cycle ends when 12 minutes have passed since the beginning of the cycle, or when the pipe temperatures (TH3
and TH6) have been continuously detected for 4 minutes (when SW4 (916) is set to OFF) or 2 minutes (when SW4 (916) is
set to ON) that exceeds the values in the table below.
The defrost cycle will not end for two minutes once started unless one of the following conditions is met : Pipe temperature
reaches 25°C [77°F] and SW4 (916) is set to OFF OR α
*1
=25°C+TH7°C [77°F+TH7°F] and SW4 (916) is set to ON.
*1 (5°C [41°F] ≤ α ≤ 25°C [77°F]).
In the multiple-outdoor-unit system, defrosting is stopped on all units at the same time.
(4) Problems during defrost operation
If a problem is detected during defrost operation, the operation will be stopped, and the defrost prohibition time based on the
integrated compressor operation time will be set to 20 minutes.
(5) Change in the number of operating indoor units during defrost operation
Even when there is a change in the number of operating indoor units during defrost operation, the operation will continue, and
an adjustment will be made after the completion of the defrost operation.
Defrost operation will be continued, even if the indoor units stop or under the Thermo-OFF conditions until it has run its course.
Outdoou unit
Compressor frequency
Model
Compressor frequency
(E)P200, (E)P250 models
79Hz
(E)P300, (E)P350, P400 models
107Hz
EP400, (E)P450, (E)P500 models
112Hz
Outdoor unit fan
Stopped
SV1a
ON (open)
SV5b
ON (closed)
21S4a, 21S4b
OFF
SV9
OFF (closed)
BC controller
LEV1
G type: 4000, GA type: 6000, HA type: 8000 (60 or 41)
LEV3
G type: 1000, GA type: 2000, HA type: 2000 (60)
GB, HB type: 60 (full closed)
SVM1
ON
SVM2
ON
SVM1b
ON
SVM2b
OFF
SVB
OFF
SVA
Ports that are connected to the indoor units in cooling Thermo-ON
Other ports : OFF
Model
TH3 and TH6
SW4 (916) OFF
SW4 (916) ON
(E)P200 model
7°C [45°F]
12°C [54°F]
(E)P250 model
7°C [45°F]
12°C [54°F]
(E)P300 model
7°C [45°F]
12°C [54°F]
(E)P350 model
7°C [45°F]
12°C [54°F]
(E)P400 model
7°C [45°F]
12°C [54°F]
(E)P450 model
7°C [45°F]
12°C [54°F]
(E)P500 model
7°C [45°F]
12°C [54°F]
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...