[8-9 Troubleshooting Problems with Major Components on BC Controller ]
- 336 -
HWE1314A
GB
8-9-5
BC Controller Transformer
* Before measuring the resistance, pull out the connector.
Normal
Abnormal
CNTR(1)-(3)
about 58 Ω.
Open-phase or shorting
CN03(1)-(3)
about 1.6 Ω.
CNTR
CN03
BC controller control board
Red
White
Red
Red
Содержание PURY-EP200YLM-A