[5-2 Outdoor Unit Control ]
- 136 -
HWE1314A
GB
5-2-5
Refrigerant Bypass Control
Bypass solenoid valves, which bypass the high- and low- pressure sides, perform the following functions.
(1) Bypass solenoid valve (SV1a) (ON = Open)
(2) Bypass solenoid valve (SV9) (ON = Open)
(3) Bypass solenoid valve (SV5b) (ON = Closed)
Operation
SV1a
ON
OFF
When starting-up the compressor of each
outdoor unit
ON for 4 minutes.
After the restoration of thermo or 3 minutes
after restart
ON for 4 minutes.
During cooling or heating operation with the
compressor stopped
Always ON.
Exception: OFF when 63HS1-63LS is 0.2MPa[29psi] or less
After the operation has stopped
ON for 3 minutes.
Exception: OFF when 63HS1-63LS is 0.2MPa[29psi] or less
During defrost operation
ON
While the compressor is operating at the
minimum frequency and when the low pres-
sure (63LS) drops (3 or more minutes after
compressor startup)
When the low pressure (63LS)
drops below 0.23 Mpa [33 psi] dur-
ing cooling-only or cooling-main op-
eration.
When the low pressure (63LS)
drops below 0.38 Mpa [55 psi] dur-
ing cooling-only or cooling-main op-
eration.
When high pressure (63HS1) rises
When 63HS1 exceeds
3.62MPa[525psi]
When 63HS1 is or below
3.43MPa[497psi] and 30 seconds
have passed
Operation
SV9
ON
OFF
When high pressure (63HS1) rises during
the heating operation
When 63HS1 exceeds 3.50MPa
[507psi]
When SV5b is ON and the pressure
is 2.70MPa[391psi]or below
Others
Always OFF
Operation
SV5b
ON (Closed)
OFF (Open)
When high pressure (63HS1) rises during
the heating operation
When the pressure is 2.70MPa
[391psi] or below
When SV9 is ON and the pressure
is 3.50MPa [507psi] or more
At startup
ON (Closed)
During defrost cycle
ON (Closed)
When returning to normal operation after
completion of the defrost cycle
OFF (Open) for 3 minutes and goes ON (Closed)
Others
Always ON (Closed)
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...