[8-3 Refrigerant Control Problems ]
- 306 -
HWE1314A
GB
Cause
Check method and remedy
3.
RPM error of the outdoor unit FAN
Refer to the following page(s).
[8-7 Troubleshooting Outdoor Unit Fan Prob-
lems](page 321)
[7-3-3 Error Code [1302] (during operation)](page
230)
Motor failure or board failure, or airflow rate de-
crease due to clogging of the heat exchanger
The fan is not properly controlled as the outdoor
temperature cannot be precisely detected by the
temperature sensor.
The fan is not properly controlled as the pressure
cannot be precisely detected by the pressure sen-
sor.
4.
Long piping length
The cooling capacity varies greatly depending on the
pressure loss. (When the pressure loss is large, the
cooling capacity drops.)
Check the piping length to determine if it is contributing
to performance loss.
Piping pressure loss can be estimated from the tem-
perature difference between the indoor unit heat ex-
changer outlet temperature and the saturation
temperature (Te) of 63LS. →Correct the piping.
5.
Piping size is not proper (thin)
6.
Insufficient refrigerant amount
Protection works and compressor frequency does
not rise due to high discharge temperature.
Refer to item 1 (Compressor frequency does not rise
sufficiently.) on the previous page.
Refer to the following page(s).[6-9 Evaluating and Ad-
justing Refrigerant Charge](page 179)
7.
Clogging by foreign object
Check the temperature difference between in front of
and behind the place where the foreign object is clog-
ging the pipe (upstream side and downstream side).
When the temperature drops significantly, the foreign
object may clog the pipe.
→ Remove the foreign object inside the pipe.
8.
The indoor unit inlet temperature is excessively.
(Less than 15°C [59°F] WB)
Check the inlet air temperature and for short cycling.
Change the environment where the indoor unit is
used.
9.
Compressor failure
The amount of circulating refrigerant decreases due
to refrigerant leak in the compressor.
Check the discharge temperature to determine if the
refrigerant leaks, as it rises if there is a leak.
10.
BC controller LEV 3 actuation failure
Sufficient liquid refrigerant is not be supplied to the
indoor unit as sufficient sub cool cannot be secured
due to LEV3 malfunction.
Refer to the following page(s).[8-8 Troubleshooting
LEV Problems](page 322)
It most likely happens when there is little difference or
no difference between TH12 and TH15.
11.
TH12, TH15 and 63HS1 sensor failure or faulty wir-
ing
LEV3 is not controlled normally.
Check the thermistor.
Check wiring.
12.
The restrictions on pipe lengths have not been ob-
served
Refer to the following page(s).[2-10-1 Restrictions on
Refrigerant Pipe Length](page 53)
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...