[5-1 Dipswitch Functions and Factory Settings ]
- 134 -
HWE1314A
GB
(2) ME remote controller (PAR-F27MEA)
Set the address of the remote controller with the rotary switch.
To set addresses, use a precision slotted screw driver [2.0 mm [0.08 in] (w)], and do not apply than 19.6N.
The use of any other tool or applying too much load may damage the switch.
5-1-4
BC Controller Switch Settings
Model setting
012
345
67
89
012
345
67
89
012
345
67
89
012
345
67
89
10's digit 1's digit
(left)
(right)
Remote controller unit
Rotary switch
Example: In case of address 108
Address setting range
Setting method
Main remote controller
101-150
Add 100 to the smallest address of all the indoor units in the
same group.
Sub remote controller
151-200
Add 150 to the smallest address of all the indoor units in the
same group.
Setting of rotary switch
Address No.
01-99
*1
101-199 with the 100's digit automatically being set to 1
*2
00
200
*1. At factory shipment, the rotary switch is set to 01.
*2. The address range that can be set with the ME remote controller is between 101 and 200. When the dials are set to
a number between 01 and 99, the 100's digit is automatically set to [1]. When the dials are set to 00, the 100's digit is
automatically set to [2].
Switch
Function
Function according to switch setting
Switch setting timing
OFF
ON
SW4
1
Model setting
R410A
-
Always leave this switch to OFF.
2 - 5
-
-
-
-
6
No. of ports
*1
*1. When a junction pipe kit was used to merge two ports to connect the indoor units with a total capacity of between P81
and P140, turn DIP SW4-6 to ON. When connecting a main and a sub BC controller, change the SW setting on only the
main BC controller. (It is not necessary to change the SW setting on the sub BC controller. )
1
2
Before being energized
7, 8
-
-
-
-
SW5
1 - 6
-
-
-
-
7
Model setting
Refer to the table below.
Before being energized
8
Model setting
Refer to the table below.
Before being energized
SW5-8
OFF
ON
SW5-7
OFF
G1 type
ON
GA1 (HA1) type
GB1 (HB1) type
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...