[4-1 Outdoor Unit Circuit Board Arrangement ]
- 97 -
HWE1314A
GB
4
Elect
rica
l Compone
nt
s
and
Wirin
g
Diag
rams
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the water-
proof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter-
minals to remove them.
3) Control box houses high temperature parts. Be well careful even after turning off the power source.
4)
Perform the service after disconnecting the outdoor unit fan board connector (CNINV) and the inverter board con-
nector (CN1). Before plugging in or unplugging connectors, check that the outdoor unit fan is not rotating and that
the voltage between SC-P and SC-N on the capacitor board is 20 VDC or less. The capacitor may collect a charge and
cause an electric shock when the outdoor unit fan rotates in windy conditions.
Refer to the wiring nameplate for details.
5) To connect wiring to TB7, check that the voltage is 20 VDC or below.
6) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1) back to the inverter board after
servicing.
7) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that
the capacitor voltage (inverter main circuit) has dropped to 20 V DC or less. It takes about 10 minutes to discharge electricity
after the power supply is turned off.
8) When the power is on, the compressor or heater is energized even while the compressor is stopped. Before turning on the
power, disconnect all power supply wires from the compressor terminal block, and measure the insulation resistance of the
compressor. Check the compressor for a ground fault. If the insulation resistance is 1.0 MΩ or below, connect all power supply
wires to the compressor and turn on the power to the outdoor unit. It is energized to evaporate the liquid refrigerant that has
accumulated in the compressor.
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...