[8-3 Refrigerant Control Problems ]
- 305 -
HWE1314A
GB
8
Trou
ble
sho
oting
Bas
ed
on
Obse
rved
Sy
mpto
ms
8-3
Refrigerant Control Problems
8-3-1
Units in the Cooling Mode Do Not Operate at Expected Capacity.
1. Phenomena
Although cooling operation starts with the normal remote controller display, the capacity is not enough
2. Cause, check method and remedy
Cause
Check method and remedy
1.
Compressor frequency does not rise sufficiently.
Faulty detection of pressure sensor.
Protection works and compressor frequency does
not rise due to high discharge temperature
Protection works and compressor frequency does
not rise due to high pressure
Pressure drops excessively.
(1)
Check pressure difference between the detected
pressure by the pressure sensor and the actual pres-
sure with self-diagnosis LED.
→ If the accurate pressure is not detected, check the
pressure sensor.
Refer to the following page(s). [8-5-1 Comparing the
High-Pressure Sensor Measurement and Gauge
Pressure](page 313)
Note: Lower inlet pressure by the low pressure sensor than
the actual pressure causes insufficient capacity.
SW4 setting (SW6-10: OFF)
For how to read the SW settings, refer to the follow-
ing page(s). [9-1-1 How to Read the LED](page 385)
(2)
Check temperature difference between the evaporat-
ing temperature (Te) and the target evaporating tem-
perature (Tem) with self-diagnosis LED.
Note: Higher Te than Tem causes insufficient capacity.
SW4 setting (SW6-10: OFF)
For how to read the SW settings, refer to the follow-
ing page(s). [9-1-1 How to Read the LED](page 385)
Note: Protection works and compressor frequency does not
rise even at higher Te than Tem due to high discharge
temperature and high pressure.
At high discharge temperature:
Refer to the following page(s).[7-3-1 Error Code
[1102]](page 228)
At high pressure:
Refer to the following page(s). [7-3-3 Error Code
[1302] (during operation)](page 230)
2.
Indoor unit LEV malfunction
Refer to the following page(s).[8-8 Troubleshooting
LEV Problems](page 322)
Insufficient refrigerant flows due to LEV malfunc-
tion (not enough opening) or protection works and
compressor frequency does not rise due to pres-
sure drop.
Refrigerant leak from LEV on the stopping unit
causes refrigerant shortage on the running unit.
High pressure sensor
Low pressure sensor
ON
SW4
1 2 3 4
5
6 7
8 9 10 OFF
ON
SW4
1 2 3 4
5
6 7
8 9 10 OFF
Evaporating temperature Te
Target evaporating temperature Tem
ON
SW4
1 2 3 4
5
6 7
8 9 10 OFF
ON
SW4
1 2 3 4
5
6 7
8 9 10 OFF
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...