[2-10 Restrictions on Refrigerant Pipes ]
- 57 -
HWE1314A
GB
2
Rest
rict
io
ns
(3) System that requires more than 16 BC controller ports or with multiple BC controllers <System with two outdoor
units>
1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes
will be used between the main and the sub BC controllers.
2) When connecting two sub BC controllers, observe the maximum allowable length in the table above.
3) When connecting two sub BC controllers, install them in parallel.
4) To connect the P100 through P140 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J1) and merge
the two ports before connecting them. (In that case, set DIP SW4-6 on the BC controller to ON.)
It is also possible to connect the P100 through P140 models of units to a port, although the cooling performance will somewhat
decrease. (In that case, set DIP SW4-6 on the BC controller to OFF.)
(The factory setting for DIP SW4-6 is OFF.)
5) Do not connect the P200 or P250 models of indoor units and other models of indoor units at the same port.
6) Group the indoor units together that connected to the same port if multiple indoor units are connected to the same port on BC
controller. Also share one thermo-stat such as on remote controller so that they turn on/off at the same time.
h1
h3
h1
h2
f
D
E
e
Outdoor Twinning kit (High/Low press.)
CMY-R100VBK-A: P400 - P500YSLM
CMY-R100VBK2: P550 - P650YSLM
CMY-R200VBK2: P700 - P800YSLM
CMY-R200XLVBK: P850 - P900YSLM
CMY-ER100VBK-A: EP500YSLM
CMY-ER200VBK: EP550 - EP900YSLM
On the low-pressure side, the twinning kit connects to the pipes on site inside the outdoor unit.
When different capacity units are combined, connect the kit to the larger capacity outdoor unit.
a
C
b
B
c
d
A
G
F
h4
Outdoor unit
1
Outdoor unit
2
H H'
h1
BC controller (main)
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
BC controller (sub)
BC controller (sub)
Branch joint
(CMY-Y202-G2)
(CMY-Y102L-G2)
(CMY-Y102S-G2)
Branch joint
(CMY-Y102S-G2)
(P15 - P80 models)
(P100 - P250 models)
Maximum of 3 units per port
Total capacity of P80 or below
Reducer (P15 - P50 models)
(Supplied with the BC Controller)
Junction pipe
(CMY-R160-J1)
Unit: m [ft]
Operation
Pipe sections
Allowable length of pipes
Length Total pipe length
F+G+A+B+C+D+E+a+b+
c+d+e+f
Refer to the restrictions on the total pip-
ing length.
Total pipe length from the outdoor unit to
the farthest indoor unit
F(G)+A+C+E+f
165 [541] or less
(Equivalent length 190 [623] or less)
Between outdoor unit and BC controller
F(G)+A
110 [360] or less
Between BC controller and indoor unit
B+d or C+D+e
or C+E+f
40 [131] or less
*1
Between indoor units
F+G
5 [16] or less
Height
differ-
ence
Between indoor
and outdoor
units
Outdoor unit above
indoor unit
H
50 [164] or less
Outdoor unit below in-
door unit
H'
40 [131] or less
Between indoor unit and BC controller
h1
15 [49](10[32]) or less
*2
Between indoor units
h2
15 [49](10[32]) or less
*2
Between the BC controller (main or sub)
and the sub BC controller
h3
15 [49] or less
Between outdoor units
h4
0.1 [0.3] or less
*1. When the total piping length between the BC controller and indoor units (P250 model excluded) exceeds 40 m [131
ft], observe the restrictions on the vertical separation and piping length on the next page.
*2. When the capacity of the connected indoor units is P200 or above, use the figures in the parentheses as a reference.
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...