[8-16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit ]
- 381 -
HWE1314A
GB
8
Trou
ble
sho
oting
Bas
ed
on
Obse
rved
Sy
mpto
ms
8-16 Troubleshooting Problems Using the LED Status Indicators
on the Outdoor Unit
If the LED error display appear as follows while all the SW4 switches and SW6-10 are set to OFF, check the items under the ap-
plicable item numbers below.
1. Error code appears on the LED display.
Refer to the following page(s). [7-1 Error Code and Preliminary Error Code Lists](page 221)
2. LED is blank.
Take the following troubleshooting steps.
(1) Refer to the section on troubleshooting the transmission power supply circuit, if the voltage across pins 1 through 3
of CNDC on the control panel is outside the range between 220 VDC and 380 VDC. [8-11-2 Troubleshooting Problems
with Outdoor Unit Transmission Power Supply Circuit](page 351)
(2) If the LED error display becomes lit when the power is turned on with all the connectors on the control board except
CNDC disconnected, there is a problem with the wiring to those connectors or with the connectors themselves.
(3) If nothing appears on the display under item (2) above AND the voltage between pins 1 and 3 of CNDC is within the
range between 220 VDC and 380 VDC, control board failure is suspected.
3. Only the software version appears on the LED display.
(1) Only the software version appears while the transmission cables to TB3 and TB7 are disconnected.
1) Wiring failure between the control board and the transmission line power supply board.(CN62, CNPS, CNIT, CNS2, CN102)
2) If item 1) checks out OK, the transmission line power supply board failure is suspected.
3) If items 1) and 2) check out OK, control board failure is suspected.
(2) If the LED shows the same display as the initial display upon disconnection of transmission lines (TB3, TB7), there
is a problem with the transmission lines or with the connected devices. [9-1-2 Initial LED Display](page 386)
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...