[7-5 Error Code Definitions and Solutions: Codes [3000 - 3999] ]
- 238 -
HWE1314A
GB
7-5
Error Code Definitions and Solutions: Codes [3000 - 3999]
7-5-1
Error Code [3121]
1. Error code definition
Out-of-range outside air temperature
2. Error definition and error detection method
When the thermistor temperature of -28°C[-18°F] or below has continuously been detected for 3 minutes during heating op-
eration (during compressor operation), the unit makes an error stop and "3121" appears on the display. (Use the OC therm-
istor temperature to determine when two outdoor units are in operation.)
The compressor restarts when the thermistor temperature is -26°C[-15°F] or above (both OC and OS) during error stop. (The
error display needs to be canceled by setting the remote controller.)
Outdoor temperature error is canceled if the units stop during error stop. (The error display needs to be canceled by setting
the remote controller.)
3. Cause, check method and remedy
Check the following factors if an error is detected, without drop in the outdoor temperature.
<Reference>
Cause
Check method and remedy
(1)
Thermistor failure
Check thermistor resistance.
(2)
Pinched lead wire
Check for pinched lead wire.
(3)
Torn wire coating
Check for wire coating.
(4)
A pin on the male connector is missing or
contact failure
Check connector.
(5)
Disconnected wire
Check for wire.
(6)
Thermistor input circuit failure on the control
board
Check the intake temperature of the sensor with the LED
monitor.
When the temperature is far different from the actual temper-
ature, replace the control board.
TH7
Open detection
-40 C [ -40 F ] and below (130 k )
Short detection
110 C [230 F ] and above (0.4 k )
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...