[7-7 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
- 260 -
HWE1314A
GB
7-7-9
Error Code [5301] Detail Code 117
1. Error code definition
ACCT sensor circuit fault (Detail code 117)
2. Error definition and error detection method
When an error value is detected with the ACCT detection circuit just before the inverter starts
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems](page 337)
7-7-10
Error Code [5301] Detail Code 119
1. Error code definition
Open-circuited IPM/Loose ACCT connector (Detail code 119)
2. Error definition and error detection method
Presence of enough current cannot be detected during the self-diagnostic operation immediately before inverter startup.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems](page 337)
Cause
Check method and remedy
(1)
INV board failure
Refer to the following page(s).
[8-10-2 Checking the Inverter Board Error Detection Circuit](page 339)
[8-10-4 Checking the Inverter for Damage at No-Load](page 339)
[8-10-5 Checking the Inverter for Damage during Compressor Operation](page 340)
(2)
Compressor failure
Refer to the following page(s).
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance Prob-
lems](page 339)
Cause
Check method and remedy
(1)
Inverter output wiring problem
Check output wiring connections.
Confirm that the U- and W-phase output cables are put through CT12
and CT22 on the INV board respectively.
(2)
Inverter failure
Refer to the following page(s).
[8-10-4 Checking the Inverter for Damage at No-Load](page 339)
[8-10-5 Checking the Inverter for Damage during Compressor Oper-
ation](page 340)
(3)
Compressor failure
Refer to the following page(s).
[8-10-3 Checking the Compressor for Ground Fault and Coil Resis-
tance Problems](page 339)
(4)
Connector contact failure (INV30YC
only)
Check the connection of connector CN10.
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...