[5-2 Outdoor Unit Control ]
- 138 -
HWE1314A
GB
5-2-6
Frequency Control
Depending on the capacity required, the frequency of the compressor is controlled to keep constant evaporation temperature
(0°C [32°F] = 0.71 MPa [103 psi]) during cooling operation, and condensing temperature (49°C [120°F] = 2.88 MPa [418 psi])
during heating operation.
The table below summarizes the operating frequency ranges of the inverter compressor during normal operation.
The OS in the multiple-outdoor-unit system operates at the actual compressor frequency value that is calculated by the OS
based on the preliminary compressor frequency value that the OC determines.
The maximum frequency during heating operation depends on the outside air temperature and the dipswitch settings.
(1) Pressure limit
The upper limit of high pressure (63HS1) is preset, and when it exceeds the upper limit, the frequency is decreased every 15
seconds.
The actuation pressure is when the high-pressure reading on 63HS1 is 3.58MPa[519psi].
(2) Discharge temperature limit
Discharge temperature (TH4) of the compressor in operation is monitored, and when it exceeds the upper limit, the frequency
is decreased every minute.
Operating temperature is 115°C [239°F].
(3) Periodic frequency control
Frequency control other than the ones performed at start-up, upon status change, and for protection is called periodic frequen-
cy control (convergent control) and is performed in the following manner.
Periodic control cycle
Periodic control is performed after the following time has passed
30 seconds after either compressor start-up or the completion of defrost operation
30 seconds after frequency control based on discharge temperature or pressure limit
The amount of frequency change
The amount of frequency change is controlled to approximate the target value based on the evaporation temperature (Te) and
condensing temperature (Tc).
Model
Frequency/cooling
Frequency/heating
Max
Min
Max
Min
P200
52Hz
10Hz
58Hz
27Hz
P250
65Hz
10Hz
74Hz
27Hz
P300
74Hz
16Hz
92Hz
29Hz
P350
95Hz
16Hz
107Hz
29Hz
P400
97Hz
16Hz
107Hz
29Hz
P450
111Hz
16Hz
124Hz
29Hz
P500
120Hz
16Hz
129Hz
29Hz
EP200
52Hz
10Hz
58Hz
27Hz
EP250
65Hz
10Hz
74Hz
27Hz
EP300
74Hz
16Hz
92Hz
29Hz
EP350
95Hz
16Hz
107Hz
29Hz
EP400
97Hz
16Hz
107Hz
29Hz
EP450
111Hz
16Hz
124Hz
29Hz
EP500
120Hz
16Hz
129Hz
29Hz
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...