[8-10 Troubleshooting Inverter Problems ]
- 340 -
HWE1314A
GB
8-10-5
Checking the Inverter for Damage during Compressor Operation
Items to be checked
Phenomena
Remedy
Put the outdoor unit into opera-
tion.
Check the inverter output volt-
age after the inverter output fre-
quency has stabilized.
<INV20Y>
1)
Overcurrent-related problems occur im-
mediately after compressor startup.
Error code : 4250
Detail code : 101, 102, 106, 107
a. Check items 8-10-2 through 8-10-4
for problems.
b. Check that high and low pressures
are balanced.
c. Check that no liquid refrigerant is
present in the compressor and that
there is no liquid backflow.
→Go to "d." when the problem per-
sists after compressor startup was
repeated several times.
If normal operation is restored,
check the belt heater for problems.
d. Check that there is a pressure dif-
ference between high and low
pressures after compressor start-
up.
→Check the high pressure with
LED monitor for changes.
Replace the compressor if there is
no pressure difference. (the com-
pressor may be locked.)
2)
There is a voltage imbalance between
the wires after the inverter output voltage
is stabilized.
Greater than the larger of the following
values: imbalance of 5% or 5V
Replace the INV board if there is a volt-
age imbalance.
Check the belt heater for problems if
there is no voltage imbalance.
→When the error occurred, liquid refrig-
erant may have been present in the
compressor.
<INV30YC>
3)
A BUS circuit error occurs immediately
after compressor startup.
Error code : 4220
Detail code : 124
a. Check that 12 VDC is supplied to
the relay at startup (Check that
LED5 lights up.)Between pins 1 (+)
and 2 (-) on the CNRY connector
b. Replace the inverter board if no
problems were found with item a.
4)
An overcurrent error occurs during oper-
ation.
Error code : 4250
Detail code : 121,122
[8-10-6 Checking the Converter for
Damage during Compressor Oper-
ation](page 341)
5)
An overcurrent error occurs immediately
after compressor startup.
Error code : 4250
Detail code :101,106,107,128
a. Check for refrigerant flooding.
b. Check for interphase voltage im-
balance.
c. Replace the INV board if no prob-
lems were found with the items a or
b.
d. If the problem persists after replac-
ing the inverter board,[8-10-3
Checking the Compressor for
Ground Fault and Coil Resistance
Problems](page 339)
6)
An overvoltage error occurs during oper-
ation.
Error code : 4220
Detail code :109,110,112
[8-10-6 Checking the Converter for
Damage during Compressor Oper-
ation](page 341)
7)
No problems were found with items 1)
through 6).
Normal[8-10-6 Checking the Con-
verter for Damage during Com-
pressor Operation](page 341)
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...