[7-3 Error Code Definitions and Solutions: Codes [1000 - 1999] ]
- 230 -
HWE1314A
GB
7-3-3
Error Code [1302] (during operation)
1. Error code definition
High pressure fault 1 (Outdoor unit)
2. Error definition and error detection method
1) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor during operation (the first detection), the out-
door stops once, turns to antirestart mode for 3 minutes, and restarts after 3 minutes automatically.
2) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor again (the second detection) within 30 min-
utes after the first stop of the outdoor unit, the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts
after 3 minutes automatically.
3) If the pressure of 3.87MPa [561psi] or higher is detected by the pressure sensor (the third detection) within 30 minutes of the
second stop of the outdoor unit, the outdoor unit will make an error stop, and the error code "1302" will be displayed.
4) If the pressure of 3.78MPa [548psi] or higher is detected more than 30 minutes after the stop of the outdoor unit, the detection
is regarded as the first detection, and the operation described in step 1 above will start.
5) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display.
6) The outdoor unit makes an error stop immediately when not only the pressure sensor but also the pressure switch detects
4.15
+0,-0.15
MPa [601
+0,-22
psi]
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Indoor unit LEV actuation failure
Perform a heating operation and check the operation.
Cooling: LEV on the indoor unit
BC controller LEV1,3,
SVM1,1b,2,2b, SVA
Heating: LEV on the indoor unit
BC controller LEV3,
SVM2,2b, SV4a,SV4b,
SV4c,SV4d
Refer to the following page(s). [8-8 Troubleshooting
LEV Problems](page 322)
(2)
BC controller LEV malfunction
Heating only or heating main : Indoor LEV 3
Defrost : LEV3
(3)
BC controller SVM1 and 2 malfunction
→Cooling only or defrost
(4)
BC controller SVA and SVC malfunction
→Cooling only or cooling main
(5)
BC controller SVB malfunction →Heating only or heating main
Solenoid valve actuation failure (SV4a, SV4b, SV4c, or SV4d)
→Cooling only or cooling main
(6)
Port address setting error.
Confirm the port address of the indoor unit.
(7)
Refrigerant service valve actuation failure
Confirm that the refrigerant service valve is fully
(8)
Short cycle on the indoor unit side
Check the indoor units for problems and correct
them, if any.
(9)
Clogged filter on the indoor unit
(10) Reduced air flow due to dirty fan on the indoor unit fan
(11) Dirty heat exchanger of the indoor unit
(12)
Indoor fan (including fan parts) failure or motor failure
Items (7) through (12) above reduce the condensing capability of
the unit, resulting in high-pressure rise during heating operation.
(13) Short cycle on the outdoor unit
Check the outdoor units for problems and correct
them, if any.
(14) Dirty heat exchanger of the outdoor unit
(15)
Outdoor fan (including fan parts) failure, motor failure, or fan con-
troller malfunction
Items (13) through (15) above reduce the condensing capability of
the unit, resulting in high-pressure rise during cooling operation.
Check the fan on the outdoor unit.
Refer to the following page(s). [8-7 Troubleshooting
Outdoor Unit Fan Problems](page 321)
(16) Solenoid valve (SV1a) malfunction
The by-pass valve (SV1a) can not control rise in high pressure.
Refer to the following page(s). [8-6 Troubleshooting
Solenoid Valve Problems](page 315)
(17) Thermistor failure (TH3, TH7)
Refer to the following page(s). 3 [3-3 Functions of the
Major Components of Outdoor Unit(page 78)
(18) Pressure sensor failure
Refer to the following page(s). [8-5-1 Comparing the
High-Pressure Sensor Measurement and Gauge
Pressure](page 313)
(19) Failure of the thermistor input circuit and pressure sensor input
circuit on the controller board
Check the sensor temperature/pressure on the LED
monitor.
(20) Thermistor mounting problem (TH3, TH7)
Check the sensor temperature/pressure on the LED
monitor.
(21) Disconnected male connector on the pressure switch (63H1) or
disconnected wire
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...