[8-10 Troubleshooting Inverter Problems ]
- 343 -
HWE1314A
GB
8
Trou
ble
sho
oting
Bas
ed
on
Obse
rved
Sy
mpto
ms
8-10-10
Checking the Fan Inverter for Damage with Load
8-10-11
Checking the Installation Conditions
Items to be checked
Phenomena
Remedy
(1)
Turn off breaker.
1)
After operation, electrical overload error
or position detection error and unit stops
within 10 seconds.
Check code: 4255, 4256, 5305, 5306
Detail code: 101, 132
Check for fan motor lock.
→If locked, change for fan motor.
If the same error is still present
after changing fan motor, change
Fan board.
→If not locked, refer to 3) & 4).
(2)
Turn on breaker.
2)
RPM error before stat-up
Check code: 5305, 5306
Detail code: 134
Change Fan board if the same
error occurs after restart.
(3)
Operate unit.
3)
Electrical current overload error during
operation
Check code: 4255, 4256
Detail code: 101
a. Check for gusts or windy conditions.
b. Go to 8-10-6 if not windy.
c. After checking 8-10-6, and there is
no problem, change Fan board.
d. If replacing Fan board doesn't re-
solve issue, change fan motor.
4)
Sensor error during operation
Check code: 5305, 5306
Detail code: 132, 133
a. Check for gusts or windy conditions.
b. If no issues with wind, but the error
is still present, change Fan board.
c. Change fan motor if Fan board
change doesn't resolve issue.
5)
Voltage overload error
Check code: 4225, 4226
Detail code: 109
a. Check for gusts or windy conditions.
b. Change Fan board if it is not windy.
6)
Load short circuit
Check code: 4255, 4256.
Detail code: 105
a. Check 8-10-7 and 8-10-8. If no prob-
lem, then check wiring forshort cir-
cuit.
b. If there is no problem with item a.
above, change fan motor.
c. If same error after motor change,
change Fan board.
7)
After RPM has stabilized, voltage unbal-
ance of 5%, or 5V.
a. If voltage is unbalanced, go to 8-10-
6
b. After checking 8-10-6, and there is
no problem, change Fan board.
c. If replacing Fan board doesn't re-
solve issue, change fan motor.
Items to be checked
Phenomena
Remedy
(1)
Check refrigerant charge.
Overcharge of refrigerant
Return to correct refrigerant
charge.
(2)
Check outdoor unit branch in-
stallation.
The branch approach <500 mm.
Make branch approach >500mm
Is the branch angle < ±15° to horizontal? Make branch angle < ±15°
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...