[7-7 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
- 259 -
HWE1314A
GB
7
Troub
le
sho
oting
Using
Erro
r Cod
es
7-7-7
Error Codes [5201, 5203]
1. Error code definition
5201
High-pressure sensor fault (BC controller PS1)
5203
Intermediate pressure sensor fault (BC controller PS3)
2. Error definition and error detection method
When a pressure sensor reading of 4.06 MPa [589 psi] or above OR 0.98Mpa[142psi] or below is detected, error codes "5201"
OR "5203" will appear.
The unit will continue its operation by using other sensors as a backup.
3. Cause, check method and remedy
7-7-8
Error Code [5301] Detail Code 115
1. Error code definition
ACCT sensor fault (Detail code 115)
2. Error definition and error detection method
When the formula "output current < 1.5 Arms" remains satisfied for 10 seconds while the inverter is in operation.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems](page 337)
Cause
Check method and remedy
(1)
High pressure sensor failure
Refer to the following page(s). [8-5-1 Com-
paring the High-Pressure Sensor Measure-
ment and Gauge Pressure](page 313)
(2)
Torn wire coating
Check for damaged wire coating
(3)
A pin on the male connector is missing or contact failure
Check whether a connector pin is missing
(4)
Disconnected wire
Check for disconnected or broken wire
(5)
High pressure sensor input circuit failure on the control board
Check the temperature detected by the sen-
sor from the LED monitor. If the temperature
is significantly different from the actual tem-
perature, replace the control board.
Cause
Check method and remedy
(1)
Inverter open output phase
Check the output wiring connections.
(2)
Compressor failure
Refer to the following page(s).
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance Prob-
lems](page 339)
(3)
INV board failure
Refer to the following page(s).
[8-10-2 Checking the Inverter Board Error Detection Circuit](page 339)
[8-10-4 Checking the Inverter for Damage at No-Load](page 339)
[8-10-5 Checking the Inverter for Damage during Compressor Operation](page
340)
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...