[6-2 MA and ME Remote Controller Functions and Specifications ]
- 162 -
HWE1314A
GB
6-2
MA and ME Remote Controller Functions and Specifications
There are two types of remote controllers: ME remote controller, which is connected on the indoor-outdoor transmission
line, and MA remote controller, which is connected to each indoor unit.
6-2-1
Function/Specification Comparison
6-2-2
Local Remote Controller Selection Tips
MA remote controller and ME remote controller have different functions and characteristics. Choose the one that better suits
the requirements of a given system. Use the following criteria as a reference.
Functions/specifications
MA remote controller
*1*2
*1. MA remote controller refers to MA remote controller (PAR-31MAA, PAR-21MAA), MA simple remote controller, and wire-
less remote controller.
*2. Either the MA remote controller or the ME remote controller can be connected when a group operation of units in a sys-
tem with multiple outdoor units is conducted or when a system controller is connected.
ME remote controller
*2*3
*3. ME remote controller refers to ME remote controller and ME simple remote controller.
Remote controller address settings Not required
Required
Indoor/outdoor unit address set-
tings
Not required (required only by a system
with one outdoor unit)
*4
*4. Depending on the system configuration, some systems with one outdoor unit may require address settings.
Required
Wiring method
Non-polarized 2-core cable
To perform a group operation, daisy-
chain the indoor units using non-polar-
ized 2-core cables.
Non-polarized 2-core cable
Remote controller connection
Connectable to any indoor unit in the
group
Connectable anywhere on the indoor-out-
door transmission line
Interlock with the ventilation unit
Each indoor unit can individually be in-
terlocked with a ventilation unit. (Set up
via remote controller in the group.)
Each indoor unit can individually be inter-
locked with a ventilation unit. (Set up via
remote controller.)
Changes to be made upon group-
ing change
MA remote controller wiring between in-
door units requires rewiring.
Either the indoor unit address and remote
controller address must both be changed,
or the registration information must be
changed via MELANS.
MA remote controller
*1*2
ME remote controller
*1*2
There is little likelihood of system expansion and group-
ing changes.
Grouping (floor plan) has been set at the time of instal-
lation.
There is a likelihood of centralized installation of remote
controllers, system expansion, and grouping changes.
Grouping (floor plan) has not been set at the time of in-
stallation.
To connect the remote controller directly to the OA pro-
cessing unit.
*1. ME remote controller and MA remote controller cannot both be connected to the same group of indoor units.
*2. A system controller must be connected to a system to which both MA remote controller and ME remote controller are con-
nected.
<System with MA remote controller>
<System with ME remote controllers>
MA remote controller
Outdoor unit
Indoor unit
BC controller
M-NET transmission line
(indoor/outdoor transmission line)
group
group
ME remote controller
Outdoor unit
Indoor unit
BC controller
M-NET transmission line
(indoor/outdoor transmission line)
group
group
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...