[6-5 Making Interlock Settings from an MA Remote Controller ]
- 169 -
HWE1314A
GB
6
T
est
Ru
n
6-5
Making Interlock Settings from an MA Remote Controller
LOSSNAY interlock setting (Make this setting only when necessary.)
6-5-1
MA Remote Controller (PAR-31MAA)
This setting is required only when the operation of City Multi units is interlocked with LOSSNAY units. This setting is not available for the
Mr. Slim units. Interlock settings can be made for the indoor unit to which the remote controller is connected. (They can also be
confirmed or deleted.)
Note:
Use the centralized controller to make the settings if it is connected.
To interlock the operation of the indoor units with the LOSSNAY units, be sure to interlock the addresses of ALL indoor
units in the group and that of the LOSSNAY unit.
[Button operation]
[1] When "Lossnay" on the Service
menu is selected, the remote
controller will automatically begin
searching for the registered
LOSSNAY addresses of the
currently connected indoor unit.
[2] When the search is completed,
the smallest address of the
indoor units that are connected
to the remote controller and the
address of the interlocked
LOSSNAY unit will appear. "--"
will appear if no LOSSNAY unit
is interlocked with the indoor
units.
If no settings need to be made, press the RETURN button to go
back to the Service menu.
To make LOSSNAY interlock setting
[3] Enter the addresses of the indoor unit and the LOSSNAY unit to be
interlocked, with the F1 through F4 buttons, select "Set" in the
"Function", and press the SELECT button to save the settings.
"Sending data" will appear on the screen. If the setting is
successfully completed, "Setting completed" will appear.
Lossnay
IU address
Lossnay address
Collecting data
Lossnay
Cursor
Address
Select:
IU address
Lossnay address
Function
Set
/Conf/Del.
Lossnay
Lossnay
Return:
IU address
Lossnay address
IU address
Lossnay address
Sending data
Setting completed
To search for the LOSSNAY address
[4] Enter the address of the indoor unit to which the remote controller is
connected, select "Conf" in the "Function", and press the SELECT button.
"Collecting data" will appear on the screen. If the signal is received correctly,
the indoor unit address and LOSSNAY address will appear. "--" will appear
when no LOSSNAY unit is found. "Unit not exist" will appear if no indoor units
that are correspond to the entered address are found.
To delete the interlock setting
[5] To delete the interlocked setting between LOSSNAY unit and the indoor units
to which the remote controller is connected, enter the indoor unit address and
LOSSNAY address with the F1 through F4 buttons, select "Del." in the
"Function", and press the SELECT button. "Deleting" will appear. The screen
will return to the search result screen if the deletion is successfully
completed. "Unit not exist" will appear if no indoor units that are correspond
to the entered address are found. If deletion fails, "Request rejected" will
appear on the screen.
Lossnay
Lossnay
Return:
IU address
Lossnay address
IU address
Lossnay address
Collecting data
Unit not exist
Lossnay
Lossnay
Return:
IU address
Lossnay address
IU address
Lossnay address
Deleting
Request rejected
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...