[8-10 Troubleshooting Inverter Problems ]
- 338 -
HWE1314A
GB
Error display/failure condition
Measure/inspection item
[1]
Inverter related errors
4250, 4255, 4256, 4220, 4225, 4226, 4230, 4240, 4260, 5301,
5305, 5306, 0403
Implement solutions that correspond to the error codes or preliminary
error codes.[7-1 Error Code and Preliminary Error Code Lists](page
221)
[2]
Main power breaker trip
Refer to the following page(s). [8-10-12 Solutions for the Main No-Fuse
Breaker Trip](page 344)
[3]
Main power earth leakage breaker trip
Refer to the following page(s). [8-10-13 Solutions for the Main Earth
Leakage Breaker Trip](page 344)
[4]
Only the compressor does not operate.
Check the inverter frequency on the LED monitor. If the frequency indi-
cates that the units are in operation, refer to the following page(s). [8-
10-5 Checking the Inverter for Damage during Compressor Opera-
tion](page 340)
[5]
The compressor vibrates violently at all times or makes an abnor-
mal sound.
Refer to the following page(s). [8-10-5 Checking the Inverter for Dam-
age during Compressor Operation](page 340)
[6]
Compressor rotation speed does not reach the specified speed.
<1> Check for problems with compressor current and heatsink temper-
ature.(page 225)
<2> Check for imbalance in power supply voltage. *Approximate target:
3% or less.
[7]
Only the fan motor does not operate.
Check the inverter frequency on the LED monitor. If the frequency indi-
cates that the units are in operation, refer to the following page(s).
[8-10-8 Checking the Fan Board Error Detection Circuit at No
Load](page 341)
[8-10-9 Checking the Fan Inverter for Damage at No Load](page 342)
[8-10-10 Checking the Fan Inverter for Damage with Load](page 343)
[8]
The fan motor shakes violently at all times or makes an abnormal
sound.
Check the inverter frequency on the LED monitor. If the frequency indi-
cates that the units are in operation, refer to the following page(s).
[8-10-8 Checking the Fan Board Error Detection Circuit at No
Load](page 341)
[8-10-9 Checking the Fan Inverter for Damage at No Load](page 342)
[8-10-10 Checking the Fan Inverter for Damage with Load](page 343)
[9]
Noise is picked up by the peripheral device
<1> Check that power supply wiring of the peripheral device does not
run close to the power supply wiring of the outdoor unit.
<2> Check if the inverter output wiring is not running parallel to the
power supply wiring and the transmission lines.
<3> Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop-
erly on the shielded wire.
<4> Meg failure for electrical system other than the inverter
<5> Attach a ferrite core to the inverter output wiring. (Contact the fac-
tory for details of the service part settings.)
<6> Provide separate power supply to the air conditioner and other
electric appliances.
<7> If the problem suddenly appeared, inverter output may have had a
ground fault. For details, refer to the following page(s). [8-10-5
Checking the Inverter for Damage during Compressor Opera-
tion](page 340)
*Contact the factory for cases other than those listed above.
[10] Sudden malfunction (as a result of external noise.)
<1> Check that the grounding work is performed properly.
<2>Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop-
erly on the shielded wire.
<3>Check that neither the transmission line nor the external connec-
tion wiring does not run close to another power supply system or
does not run through the same conduit pipe.
* Contact the factory for cases other than those listed above.
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...