
[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
- 249 -
HWE1314A
GB
7
Troub
le
sho
oting
Using
Erro
r Cod
es
7-6-16
Error Code [4230] Detail Code 126
1. Error code definition
DCL temperature fault (Detail code 126)(outdoor unit)
2. Error definition and error detection method
When DCL temperature that equals or exceeds 170°C is detected (applicable to INV30YC only)
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems](page 337)
7-6-17
Error Code [4240]
1. Error code definition
Overload protection
2. Error definition and error detection method
If the output current of "(Iac) >Imax (Arms)" or "THHS > TOL" is continuously detected for 10 minutes during inverter operation.
refer to the following page(s). [7-1 Error Code and Preliminary Error Code Lists](page 225)
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems](page 337)
Cause
Check method and remedy
(1)
Fan inverter board fault
Refer to the following page(s). [8-10-8 Checking the Fan Board Error Detection Cir-
cuit at No Load](page 341)
Refer to the following page(s). [8-10-9 Checking the Fan Inverter for Damage at No
Load](page 342)
Refer to the following page(s). [8-10-10 Checking the Fan Inverter for Damage with
Load](page 343)
(2)
Outdoor unit fan fault
Check the outdoor unit fan for proper operation.
If there is a problem with fan operation, check the fan motor. Refer to the following
page(s). [8-10-7 Checking the Fan Motor for Ground Fault and Coil Resistance
Problems](page 341)
(3)
DCL temperature sen-
sor connector contact
failure
Check the connector (CNTH) on the inverter board for proper connection.
(4)
DCL error
If the problem persists after restart, replace the DCL.
Cause
Check method and remedy
(1) Air passage blockage
Check that the heat sink cooling air passage is not blocked
(2) Power supply environment
Power supply voltage is 342 V or above.
(3) Inverter failure
Refer to the following page(s). [8-10 Troubleshooting Inverter Problems](page
337)
(4) Compressor failure
Check that the compressor has not overheated during operation.
→ Check the refrigerant circuit (oil return section).
Refer to the following page(s). [8-10-3 Checking the Compressor for Ground
Fault and Coil Resistance Problems](page 339)
(5) The model selection switches
(SW5-3 - 5-8) on the outdoor
unit are set incorrectly.
Check the setting for the model selection switch on the outdoor unit (Dipswitches
SW5-3 - 5-8 on the outdoor unit control board).
For switch settings, refer to the following page(s). [7-9-2 Error Code [7101]](page
286)
Содержание PURY-EP200YLM-A
Страница 9: ...viii ...
Страница 13: ... 2 HWE1314A GB ...
Страница 29: ... 1 5 Cautionary notes on installation environment and maintenance 18 HWE1314A GB ...
Страница 31: ... 20 HWE1314A GB ...
Страница 44: ... 2 6 System Connection Example 33 HWE1314A GB 2 Restrictions ...
Страница 58: ... 2 7 Example System with an MA Remote Controller 47 47 HWE1314A GB 2 Restrictions ...
Страница 77: ... 66 HWE1314A GB ...
Страница 105: ... 94 HWE1314A GB ...
Страница 125: ... 4 6 BC Controller Circuit Board Components 114 HWE1314A GB 4 6 2 Four Relay Board 4 6 3 Ten Relay Board ...
Страница 137: ... 126 HWE1314A GB ...
Страница 171: ... 160 HWE1314A GB ...
Страница 227: ... 6 11 Standard Operation Data Reference Data 216 HWE1314A GB ...
Страница 230: ... 219 HWE1314A GB 7 9 9 Error Code 7113 292 7 9 10 Error Code 7117 293 7 9 11 Error Code 7130 294 ...
Страница 231: ... 220 HWE1314A GB ...
Страница 393: ... 8 16 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 382 HWE1314A GB ...
Страница 395: ... 384 HWE1314A GB ...