16 - 38
16. SERVO AMPLIFIER CONNECTION
16.6 Device Range that Can Be Set
*1
Use 1 to 50 of PA, PB, PC, PD, and PO when the GOT
writes data to RAM of the servo amplifier.
Use 1001 to 1050 of PA, PB, PC, PD, and PO when the GOT
write data to E
2
PROM of the servo amplifier.
Use PA, PB, PC, PD, PO 1001 to 1050 when reading
parameters to the servo amplifier RAM.
*2
When the GOT writes data to point tables, use 1001 to 1255
of POS, SPD, ACT, DCT, DWL, AUX, and MCD (E
2
PROM
area).
Even if the GOT writes a value to POS, SPD, ACT, DCT,
DWL, AUX, or MCD (1 to 255) in the RAM area, the value is
not reflected.
*3
MCD cannot be used as a real number.
*4
Only reading is possible.
*5
The GOT cannot read or write data from/to consecutive
devices.
*6
Only reading is possible for DI0 to DI4.
POINT
POINT
POINT
Precautions for SP, OM, TMB, TMI, TMO, and TMD
devices
(1) For bit devices
Only writing is possible.
[Alternate] of a bit switch cannot be used.
Use [Set], [Reset], and [Momentary] of a bit
switch.
(2) For word devices, double word devices
Only writing is possible.
Numerical input cannot be used.
When writing, use [Word Set] of a data set switch.
The following shows correspondences between virtual
devices for servo amplifier and data of the servo
amplifier used with the GOT.
(a) Servo amplifier request
(b) Operation mode selection
(c) Instruction demand (for test operation)
(d) Basic setting parameter
*1
For the parameters prefixed by an asterisk (*), setting
becomes effective when the power is turned off once and
back on after setting the parameter data.
Device
name
Item
Symbol
SP0
Status display data clear
―
SP1
Current alarm clear
―
SP2
Alarm history clear
―
SP3
External input signal prohibited
―
SP4
External output signal prohibited
―
SP5
External input signal resumed
―
SP6
External output signal resumed
―
Device
name
Item
Symbol
OM0
Normal mode (not test operation mode)
―
OM1
JOG operation
―
OM2
Positioning operation
―
OM3
Motorless operation
―
OM4
Output signal (DO) forced output
―
OM5
One step sending
―
Device
name
Item
Symbol
TMB1
Temporary stop command
―
TMB2
Test operation (positioning operation) start
command
―
TMB3
Forward rotation direction
―
TMB4
Reverse rotation direction
―
TMB5
Restart for remaining distance
―
TMB6
Remaining distance clear
―
Device name
Item
Symbol
*1
PA1, PA1001
Control mode
*STY
PA2, PA1002
Regenerative brake option
*REG
PA3, PA1003
Absolute position detection
system
*ABS
PA4, PA1004
Function selection A-1
*AOP1
PA5, PA1005
Feeding function selection
*FTY
PA6, PA1006
Electronic gear numerator
*CMX
PA7, PA1007
Electronic gear denominator
*CDV
PA8, PA1008
Auto tuning mode
ATU
PA9, PA1009
Auto tuning response
RSP
PA10, PA1010
In-position range
INP
PA11, PA1011
Forward torque limit
TLP
PA12, PA1012
Reverses torque limit
TLN
PA13, PA1013
For manufacturer setting
―
PA14, PA1014
Rotation direction selection
*POL
PA15, PA1015
Encoder output pulses
*ENR
PA16 to PA18,
PA1016 to PA1018
For manufacturer setting
―
PA19, PA1019
Parameter block
*BLK
Содержание GT15
Страница 2: ......
Страница 34: ...A 32 ...
Страница 92: ......
Страница 110: ...2 18 2 DEVICE RANGE THAT CAN BE SET 2 9 MELSEC WS ...
Страница 134: ...3 24 3 ACCESS RANGE FOR MONITORING 3 7 Connection to the Head Module of CC Link IE Field Network System ...
Страница 186: ...5 10 5 BUS CONNECTION 5 2 System Configuration ...
Страница 218: ...5 42 5 BUS CONNECTION 5 4 Precautions ...
Страница 254: ...6 36 6 DIRECT CONNECTION TO CPU 6 6 Precautions ...
Страница 286: ...7 32 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Страница 350: ...8 64 8 ETHERNET CONNECTION 8 5 Precautions ...
Страница 368: ...9 18 9 MELSECNET H CONNECTION PLC TO PLC NETWORK 9 5 Precautions ...
Страница 420: ...11 26 11 CC Link IE CONTROLLER NETWORK CONNECTION 11 5 Precautions ...
Страница 440: ...12 20 12 CC Link IE FIELD NETWORK CONNECTION 12 5 Precautions ...
Страница 490: ...13 50 13 CC Link CONNECTION INTELLIGENT DEVICE STATION 13 5 Precautions ...
Страница 510: ......
Страница 564: ...15 54 15 INVERTER CONNECTION 15 7 Precautions ...
Страница 668: ......
Страница 712: ...21 12 21 MULTIPLE GT14 GT12 GT11 GT10 CONNECTION FUNCTION 21 5 Precautions ...
Страница 713: ...MULTI CHANNEL FUNCTION 22 MULTI CHANNEL FUNCTION 22 1 ...
Страница 714: ......
Страница 760: ...22 46 22 MULTI CHANNEL FUNCTION 22 5 Multi channel Function Check Sheet ...
Страница 761: ...FA TRANSPARENT FUNCTION 23 FA TRANSPARENT FUNCTION 23 1 ...
Страница 762: ......
Страница 860: ...REVISIONS 4 ...
Страница 863: ......