Power Network Application Trainer
– Earthing / Grounding network impedance measurement
81
4.1 Earth resistance measurement exercises
4.1.1 3-Pole and 4-Pole earth resistance measuring method
4.1.1.1 Measurement with MI 3290 Earth Analyzer
4.1.1.1.1 3 Pole measuring method
Figure 60-2: 3-pole earth resistance measurement with MI 3290
Exercise is used to practice impedance measurement of single pylon installation without
connected ground wire.
3-pole method uses three-wire connection, with the possibility of frequency selection
from 55 Hz to 15 kHz (fixed / sweep mode). In this exercise, fixed frequency
measurement is used (329 Hz).
Switch position Simulated condition
Application
Expected result
Regular measurement place
condition (simulated resistive earth
character), single frequency
measurement
Industrial areas
Transformer stations
Radio towers
Pylons ground wire connection
Solar power plants
Wind & water turbine
Ze = 2,56
Ω @ 329 Hz
Table 14-2: Measurement setup/result for 3-pole measurement method