Power Network Application Trainer
– Earth / Ground network impedance analysing
147
5. Select function
CURRENT GEN.
(by using
buttons) and press
TEST
key
- presented symbol shows, that the output power is not set to maximum
Generated current by the MI 3290 is 0,49 A (up to 55 A maximim, depends on the
current probe resistance). This value should be entered into MI 3295M meter as
reference current for calculated the real Contact voltage. After finishing the
measurements, result synchronisation should be done with the station, to make
recalculation of Step voltages with the exact generated current.
MI 3295M instrument:
6. Select U CONTACT/TOUCH function by using
buttons
7. Set the parameters by using the navigation buttons
- Iset
– generated current from the MI 3290 instrument
0,49A in our test case
- Iflt
– expected fault current (defined for the test object)
5.0 kA for the test
object
- Rinp
– MI 3295M input impedance:
1.0 kΩ for measuring step/contact voltage –
selected value
2.0 kΩ for measuring step/contact voltage for Australia market by
using special adapter
1.0 MΩ for measuring ground potential rise (GPR)
- Ulim
– limit Step (Contact) voltage (calculated to real condition). Limit depends
on the type of object
200 V selected value for the test object
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...