Power Network Application Trainer
– Power generator, transformer, coils
166
Winding connection designations
First Symbol
High Voltage: Always capital letters
D
=Delta,
Y
=Star,
N
=Neutral
Second Symbol
Low voltage: Always Small letters
d
=Delta,
y
=Star,
z
=Interconnected star,
n
=Neutral
Third Symbol
Phase displacement (lagging), expressed as number from 1
to 11 (phase displacement is calculated as
n*30°)
1 = 30°, 2 = 60° …. 11 = 330°
Example:
Dyn5:
Primary winding: Delta connection
Secondary winding: Star connection, with the star point brought out (n)
and 150°
phase shift (lagging).
Supported vector groups in MI 3280 meter you can find in Instruction manual, which
could be downloaded from our web site
http://www.metrel.si/download-center.html
Selection of transformer vector group depends on different factors:
- Parallel operations:
All transformers should have same vector
group & polarity of the winding
- Removing harmonics: Dy vector group
– y winding nullifies the 3rd
harmonics
- Earth fault Relay: z or y vector group on secondary side should be used
with neutral and possible earth fault relay
- Type of transformer application: power export transformers (Dy), power
export import transformer (Yy). Yd or Dy connection is standard
connection used in practice
Metrel instrument MI3280 offers transformer winding resistance and turn ratio
measurement for single and three phase’s transformers.
MI 3280 Digital Transformer Analyzer are designed according relevant standards:
IEC 60076-1
Power transformers
– Part 1: General
IEEE C57.12.90
Standard Test Code for Liquid-Immersed Distribution,
Power, and Regulating Transformers
IEC 61869-2
Instrument transformers
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...