Power Network Application Trainer
– Earthing / Grounding network impedance measurement
57
2.3.2.1 2
–pole measurement – single frequency and sweep mode up
to 15 kHz
The two-pole measurement can be used in case, that there is a well-grounded auxiliary
terminal available (e.g. source/ distribution earthing’s via the neutral conductor, water
pipeline…). The main advantage of this method is that no test probes are needed for
the test. The method is fast and relatively reliable, but practical usage is limited with the
existing well-grounded system.
Figure 35-2: 2
– pole measurement
Notes:
AC test current I
e
is injected through the test probe H (fixed or sweep mode, 55
Hz … 15 kHz),
Impedance of probe H should be as low as possible (to inject higher test current),
Existing grounded system (conductive water pipeline) should be
“good” enough,
that its resistance is negligible,
Measured earthing system should be far enough away from the water pipeline
system to be outside its influence.
2.3.2.2 3
–pole measurement – single frequency and sweep mode
up to15 kHz
The 3 - pole measurement is the standard earthing test method. The measurement is
performed with two earthing probes (H and S), the third one is tested earthing electrode
system. The drawback by using 3
– pole measurement method is that the resistance of
the common test lead (E) is added to the final result.
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...