![METREL MI 3298 Скачать руководство пользователя страница 129](http://html1.mh-extra.com/html/metrel/mi-3298/mi-3298_instruction-manual-with-exercises_1778927129.webp)
Power Network Application Trainer
– Earthing / Grounding network impedance measurement
129
To get total object impedance, we need to calculate it from the individual values. Four
legs pylon could be presented as parallel connection of four impedances, so the
calculated object impedance is:
Foot Nm. 1
14,76
Ω
Foot Nm. 2
348
Ω
Foot Nm. 3
1,767k
Ω
Foot Nm. 4
6,62
Ω
Total impedance
4,49
Ω
Table 42-
2: Pylon’s foot impedance calculation
Measurement for the third
pylon
leg
finished
successfully.
Reposition
flex clamp to the fourth leg
and press
to
procced with measurement
Measurement finished
succesfully.