![METREL MI 3298 Скачать руководство пользователя страница 58](http://html1.mh-extra.com/html/metrel/mi-3298/mi-3298_instruction-manual-with-exercises_1778927058.webp)
Power Network Application Trainer
– Earthing / Grounding network impedance measurement
58
Figure 36-2: 3
– pole measurement
Notes:
AC test current I
e
is injected through the test probe H (fixed or sweep mode, 55
Hz … 15 kHz)
Impedance of probe H should be as low as possible (to inject higher test current),
Voltage drop is measured between probe S and E,
Use short test lead E, to minimize its influence in the final result.
2.3.2.3 4
–pole measurement – single frequency and sweep mode
up to 15 kHz
The advantage for using of 4 - pole test is that the leads and contact resistances
between measuring terminal E and tested item do not influence the measurement.
Figure 37-2: 4
– pole measurement
Notes:
AC test current I
e
is injected through the test probe H (fixed or sweep mode, 55
Hz … 15 kHz),
Impedance of probe H should be as low as possible (to inject higher test current),
Voltage drop is measured between probe S and ES,
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...