Power Network Application Trainer
– Earthing / Grounding network impedance measurement
134
Switch setup position:
Expected result:
Switch setup position:
Expected result:
Results comparison:
Table 46-2: Result comparison (Impulse method vs different test object setup)
Comparing results, we can see, that inductive earthing type has huge impact to impulse
earth impedance, which could be critical (check explanation of inductive influence
explained under item 2.5) in case of lightning strike (damage on the object and
equipment).