Power Network Application Trainer
– Power generator, transformer, coils
178
For measuring transformer turn ratio never apply AC voltage on primary or
secondary winding terminals marked as H (terminals U, V, W) or X (terminals
u, v, w), risk of electric shock! For measuring Transformer turn ratio use Metrel
instruments described in this manual
Never apply AC voltage to “pe” terminal. This terminal represents housing of
transformer.
Never touch the test terminals during the performed measurement. Risk of
electric shock.
For measuring Transformer turn ratio use Metrel instruments described in this
manual
Setup switch Nm. 4 to position 1:
Method used
Simulated condition
Expected result
r
A
= 10.107
Ω,
∆
r = 0.32% @ Uex =80V
r
B
= 10.090
Ω,
∆
r = 0.15% @ Uex =80V
r
C
= 10.109
Ω,
∆
r = 0.34% @ Uex =80V
Table 55-3: Transformer turn ratio measuring setup/result presentation
Measuring procedure
1. Under
RATIO
test menu select
r
A. B, C
measurement function
2. Set the parameters by clicking the bottom left dark grey corner
3. Take care that entered data corresponds to the transformer nominal data. These
data are presented on the transformer nominal plate. Check:
- H-X configuration
- Vector group
- Nominal primary voltage
- Nominal secondary voltage
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...