Power Network Application Trainer
– Earthing / Grounding network impedance measurement
97
Since there is simulation of ground wire connection also “impedance of neighbourhood
pylons is included” (in our case simulated inductance connected to the earth). From the
results, we can see, that the 4-Pole method is not proper one for measuring pylons
earth impedance connected via ground wire.
Result comparison:
Table 22-2: Result comparison: same test method vs different test object setup
4
– Pole / 329 Hz
3,32 Ω
3,94 Ω
1,46 Ω
1,48 Ω