![METREL MI 3298 Скачать руководство пользователя страница 109](http://html1.mh-extra.com/html/metrel/mi-3298/mi-3298_instruction-manual-with-exercises_1778927109.webp)
Power Network Application Trainer
– Earthing / Grounding network impedance measurement
109
Previous exercises describe the measurement procedure with one flex-clamp and step
by step measurement (example 2), following exercises will show procedure using one
flex-clamp but measuring of two foots together and all four foots in one step.
4.1.3.5.1 S
– Flex measuring method by using one Flex-clamp with
simulated
regular pylon’s foot condition and resistance
earth character
– measuring of two foots together
Figure 71-2: S-
Flex measurement setup for measuring two pylon foot’s
Switch position Simulated condition
Application
Expected result
Regular measurement place
condition (simulated resistive earth
character), flex measurement,
simulated ground wire connection
Pylons (mono and multi-leg)
with and without protective earth
cable connection
Ski lifts
Radio towers
Foot Nm. 1& 2 approx. 6,27 Ω
Foot Nm. 3 & 4 approx. 4,61 Ω
Z
tot calc
= 2,65 Ω
Table 32-2:
S-Flex measurement setup/result presentation
Measuring procedure
1. Follow the measurement setup connection described under 4.1.3.1 exercise. Connect
setup switches and ground wire accordingly. Take care that flex-clamp will be installed
around two pylon legs (around 1&2 in the first measurement and around 3&4 in the
second step).
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...