Power Network Application Trainer
– Earth / Ground network impedance analysing
150
2. Connection diagram and parameter settings:
- connect the black test probe to H (C1) terminal and other part to the
“current probe”
R
CS
- connect the blue test probe to E(C2) terminal and other part to the
pylon
- connect the green test probe to the S (P1) terminal and other part to the
test probe (which will be used for simulation as voltage test probe)
- Prepare test point plan, as it is presented on the picture bellow:
Figure 88-2: Test point selection for GPR measurement
Setup test parameters
. Select the test frequency (range from
55Hz to 329Hz), Step Size and Direction.
Note: Step Size present index at which point measurement is done (number of
measurement).
Note: Since potential earth spike could not be used on the training module, Metrel
propose to use test probe.
Put the test probe on the first measurement point, labelled with n=0 and press START
key
on the instrument or icon
on the LCD: