Power Network Application Trainer
– Insulation Analysis
209
Method used
Simulated condition
Expected result
Un=5 kV; T = 1 min; AVG=0
Un=5 kV; T = 1 min; AVG=5
Riso = 1,92GΩ
Riso = 1,90 GΩ
Table 72-3: Insulation resistance measuring setup/result presentation
Measuring procedure
1. Under
MAIM MENU
MEASUREMENTS
menu select
Insulation Resistance
Test
measurement function
2. Set the parameters by clicking the bottom left dark grey corner
Un
Test voltage
– step 50 V (50 V – 1 kV) and 100 V (1 kV – 10 kV).
Note: Maximum test voltage is 5 kV!
Timer1
Duration of measurement (mm:ss)
– step 1 s (max time 99 min).
Lim
Limit value selection
(OFF, 0.50 MΩ – 1.0 TΩ). If limit is not set, there
is no PASS/FAIL indication after performed measurement.
AVG
Averaging of the result value (OFF, 5, 10, 30, 60).
3. Connect the test leads to the instrument and to the test object.
- Connect the red test probe (
+Rx
) to the left test terminal on MI 3298 T
training module
- Connect the black crocodile (
-Rx
) to the right test terminal on MI 3298 T
training module
Note: Test connection for the specific test object could be checked under
HELP
menu.
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...