Power Network Application Trainer
– Earthing / Grounding network impedance measurement
95
Expected result:
Comparing the result measured with exercise under Nm.1 (Item 4.1.1.1.2)
– 2,55 Ω vs
3,94
Ω:
- There is no big (critical) difference between the both values (in case, that
value of 3,94
Ω is too high for the selected object)
- Measurement with S-Flex method will show us, that result 3,94
Ω is not
acceptable due to the broken foot’s connection. Four pole measurement
method does not show us the separate foot condition, so differen
measurement method should be choosen.
4.1.2.3 Simulation of resistance/inductive earth character, regular
foot’s condition and simulated Ground Wire connection
Figure 66-2: 4-pole earth measurements setup with MI 3290