Power Network Application Trainer
– Power generator, transformer, coils
169
Figure 96-3: Turn ratio measurement of three-phase transformer
Notes:
Consider displayed warnings when starting the measurement!
If error notification appears on screen at the beginning of the measurement
(for example V(H1-H2) > 10.0V), transformer might be supplied with auxiliary
power source. Inspect what might be the cause for that error, eliminate the
fault and try again.
If overvoltage protection notification appears on screen, first decrease the
excitation voltage and try again. If overvoltage protection is perpetually
popping up, H and X clamps are not connected properly! Check connection
any try again.
If over-current protection notification appears on screen, decrease the
excitation voltage and try again.
5.2 Winding resistance [R, R
A
, R
B
, R
C
]
MI3280 measures winding resistance by applying a stable DC current to the
appropriate winding (or winding combination). After detecting steady state of winding
current, the voltage is measured and resistance is calculated by Ohm’s law. When
measurement is finished, the transformer inductance is discharged with internal
circuitry and the energy is redirected back to the battery. Such energy recuperation is
extending the autonomy of the battery.
5.2.1 Single phase transformers
Single-phase transformer winding resistance testing is divided into two parts:
measurement of resistance of high voltage winding (H)
measurement of resistance of low voltage winding (X)
MI 3280 DT Analyser has a single current source, so winding resistances is
measured sequentially (one by one).
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...