Power Network Application Trainer
– Earth / Ground network impedance analysing
138
- Ulim
– limit Step voltage. Limit depends on the type of object attached to the
measured object
200 V for selected case
7. Placement of measuring probes:
Note
:
for measuring step voltages, different directions around test object should be
tested
8.
Press “TEST” button on the MI 3295M instrument to start measurement:
Where:
- Um
– measured voltage between test probes
- U
– calculated “real” step voltage
Um* I
flt
/I
set
)
Measured Step voltage is below the specified limits, so there is PASS indication.