Power Network Application Trainer
– Earthing / Grounding network impedance measurement
92
4.1.2 4 Pole measuring method
– simulated different test object state
4.1.2.1 Simulation of inductive earth character, regular pylon
foot’s condition
Figure 64-2: 4-pole earth measurements setup with MI 3290
Switch position
Simulated condition
Application
Expected result
Regular measurement place
condition (simulated inductive
earth character), single and
sweep frequency
measurement
Industrial areas
Transformer stations
Radio towers
Pylons without ground wire
connection
Solar power plants
Wind &water turbine
Ze = 3,32
Ω @ 329 Hz, single mode
Ze = 3,31
Ω@ sweep mode
Table 19-2: Measurement setup/result for 4-pole method
Measurement setup and procedure is the same as under exercise Nm. 1 (Item
4.1.1.1.2), so check the details for proper connection.
Select proper switch position on the training module.