Power Network Application Trainer
– Earthing / Grounding network impedance measurement
68
Figure 49-2: Influence of inductive impedance part at 3-pole measurement
From this example it is visible, that increased impedance during voltage strike could
cause significant problems, if earthing system is not properly done and serious hazard
to people or equipment.