Power Network Application Trainer
– Earthing / Grounding network impedance measurement
114
Measuring procedure:
1. Select proper switch position on the training module:
2. Under
Test
function select the
PGWT
measurement method
3. Connect measuring cables according the connection diagram
- connect the black test probe to H (C1) and GUARD terminal and other part to
the
“current probe”
R
CE
- connect the blue test probe to E(C2) terminal and other part to the
pylon
- fit the S-Flex clamp around
all four foots
Note: Current for all tower foots have to be measured!
4. Setup the parameters, test frequency and number of turnings
5. Start the measurement by pressing START key
on the instrument or icon
on the LCD
Содержание MI 3298