![METREL MI 3298 Скачать руководство пользователя страница 108](http://html1.mh-extra.com/html/metrel/mi-3298/mi-3298_instruction-manual-with-exercises_1778927108.webp)
Power Network Application Trainer
– Earthing / Grounding network impedance measurement
108
To get total object impedance, we need to calculate it from the individual values. Four
legs pylon could be presented as parallel connection of four impedances, so the
calculated object impedance is:
Foot Nm. 1
47,2
Ω
Foot Nm. 2
16,11
Ω
Foot Nm. 3
30,3
Ω
Foot Nm. 4
7,25
Ω
Total impedance
3,93
Ω
Table 30-
2: Pylon foot’s impedance
4.1.3.5 S
– Flex measuring method by using one Flex-clamp with
simulated
regular pylon’s foot condition and resistance earth
character
Depends on the tower dimensions, different approach could be used, related to the
measurement object:
1. Mono pylon
–
one flex-clamp
2. Four (4) legs pylon -
one flex-clam
3. Four (4) legs pylon
– four flex-clamps
One (1) flex used
One measurement
One (1) flex used
Four (4)
– one by one –
measurements
Time
consuming,
complex post analyses
with
additional
calculation
Four (4) flex used
One measurement
4. Four (4) legs pylon
–
two flex-clamps
5. Larger objects
–
more
flex-
clamps
“joined”
together
Two (2) flex used (circumference
2x5m=10m)
One measurement
Up to four (4) flex used
(circumference up to 4x5m=20m)
One measurement
Table 31-2: Flex clamp installation
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...