Power Network Application Trainer
– Earthing / Grounding network impedance measurement
61
Notes:
AC test current I
e
is injected through the test probe H (25 kHz)
Impedance of probe H should be as low as possible (to inject higher test current),
Voltage drop is measured between probe S and E,
Earth resistance Re is determined from the voltage U
S-E
and I
e
.
HF-Earth resistance (25 kHz) measurement method automatic compensate inductive
components of the adjacent pylons.
Figure 41-2: Compensation of inductive component with HF 25 kHz method
Note:
Typical ground wire inductance in power lines 0.2 mH
– 200 mH
2.3.2.7 Selective (Flex Clamps 1 - 4) measurement
– single
frequency and sweep mode up to 1.5 kHz
This measurement is applicable for measuring selective earth resistances of individual
earthing points in an earthing system (example: pylon foots, antenna towers etc.). The
earthing rods do not need to be disconnected during measurement.
Figure 42-2: Selective (Flex Clamps 1-4) measurement