Power Network Application Trainer
– Power generator, transformer, coils
168
Specifics for measuring CT's:
For measuring the CT turn ratio connect high voltage winding to X clamps and
low voltage winding to H clamp.
When measuring small currents transformers (CTs), it is recommended to start
with low Vex (1 V), to prevent the core saturation at higher voltages. After
successfully completing the first measurement, gradually increase the Vex and
repeat measurements to get better accuracy of results. If the transformer core
become saturated during measurement this will result in excitation current (i)
that is NOT in proportion with Vex and will also result in phase (
ϕ
) that vary
almost randomly. In such case treat such result as NOT valid. Use result at
smaller Vex as valid one.
5.1.2 Three - phase transformers
Before performing measurement, basic transformer data should be entered into the
instrument:
- H-X configuration
- Vector group (this info could be found on the transformer name plate
and is fundamental parameter for performing correct measurements)
- excitation voltage
- excitation frequency
- primary/secondary voltage
- TAP position
Notes:
MI 3280 DT Analyser has a single AC source, so multiple phases of the three-
phase transformer are measured sequentially (phase A, B and C). It is
suggested to keep Vex as high as possible (Vex = 80 V), if this is not in
conflict with safety procedures, testing procedure or violating transformer
maximum voltage.
It is highly recommended to set excitation frequency (fex) to 70 Hz, if no
specific reason exists to set differently. This frequency is the most suitable
choice for both 50 Hz and 60 Hz grid system.
During the transformer turn ratio also phase deviation is calculated and presented on
the LCD screen (phase difference of first harmonic (@fex) between high voltage
winding (H) voltage and low voltage winding (X) voltage).
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...