5.1 Turn ratio test [r, r
A
, r
B
, r
C
]
5.1.1 Single phase transformers
Transformer turn ratio (r) for single phase transformer could be measured for CT
–
current transformer or VT/PT
– voltage/power transformers. Before performing
measurement, basic transformer data should be entered into the instrument:
- type of transformer
- reference turn ratio
- excitation voltage
- excitation frequency
Notes:
Please set parameter transformer Type prior measurement and check specific
connections. Special care should be taken during measuring of current
transformer.
Use Vex as high as possible (Vex = 80 V), because the accuracy will be higher in
comparison with low excitation voltages. This setting must not be in conflict with
any safety procedures or with transformer maximum allowable applied voltage.
Check these values prior starting the measurement.
If you do not have specific reason to operate at specific excitation frequency, it is
highly recommended to set fex to 70 Hz.
Consider displayed warnings when starting the measurement!
If error notification appears on screen at the beginning of the measurement (for
example V(H1H2) > 10.0V), transformer might be supplied with auxiliary power
source. Inspect what might be the cause for that error, eliminate the fault and try
again.
If overvoltage protection notification appears on screen, first lower the excitation
voltage and try again. If overvoltage protection is perpetually popping up, H and X
clamps are not connected properly! Check connection any try again.
If over current protection notification appears on screen, lower the excitation
voltage and try again.
During the transformer turn ratio also phase deviation is calculated and presented on
the LCD screen (phase difference of first harmonic (@fex) between high voltage
winding (H) voltage and low voltage winding (X) voltage).
Figure 95-3:
Single-phase VT/PT transformer and CT transformer turn ratio measurement
connection
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...