Malfunctions
80
Table 13.13 Boiler controlled pump
Display:
Boiler contr P
Description:
Boiler controlled pump malfunction
Cause and Remedy:
pump unplugged
► plug in pump, check cable connections
power too high
► too low adjusted, pump sticks or is defective
power too low
► too high adjusted, pump sticks or is defective
pump is sticking
make the pump easy-running
pump defective
► replace pump
Table 13.14 Safety temperature limiter and Low H2O / —F1
Display:
Safety T sys
Description:
Safety temperature limiter has tripped
Cause and Remedy:
safety temperature limiter
unplugged
► connect up safety temperature limiter and check cable
connections
safety temperature limiter
has tripped
► check boiler controller
safety temperature limiter
defect
► allow boiler to cool and reset alarm
Display:
Low H2O/ – F1
Description:
Low H2O has been actuated
Cause and Remedy:
low H2O unplugged
► connect up low H2O and check cable connections
low H2O button has been
pressed
► reset low H2O switch
low H2O defect
► replace low H2O switch
fuse –F1of controller
defective
► replace fuse –F1 of controller
Table 13.15 Wrong system
Display:
Wrong system
Description:
The wrong program has been saved to the boiler controller
Cause and Remedy:
wrong program
► upload and save the correct program to the boiler
controller — see appendix
Table 13.16 External de-ashing system (optional)
Display:
Ash box full
Description:
The alarm text "Ash box full" is displayed after the motor has made 3 unsuccessful
attempts to reach the normal speed of the external de-ashing system.
Cause and Remedy:
Ash box is full
► Empty ash box, reset alarm text by pressing Enter.
The status of the boiler is displayed on screen.
Ash box is not securely
mounted
► Check position of ash box and adjust if required.
Installation Manual PES 36–56
PE 3671 USA 2.3
Содержание Pellematic PES 12-20
Страница 38: ...Connecting up to the power supply 38 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 46: ...Connecting up to the power supply 46 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 47: ...Connecting up to the power supply 47 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 52: ...Operating the pellet boiler 52 Setting date and time Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 88: ...Appendix 88 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 92: ...Appendix 92 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 99: ...Appendix 99 Labeling 105x74 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 100: ......