Starting up for the first time
63
P160
Fuel Corr.
P160: Step:00
The burner auger running duration is calculated automatically
by the PLC depending on the rated power and the boiler
setpoint temperature. The burner motor is controlled
accordingly. You can reduce or increase the value calculated
by the PLC 10 steps up or down.
yes
0
P161
Ext Auger delay
P161: 0
Delay of the extraction auger in compare to the burner auger
– only for Auger delivery systems.
P162
Modulation level
P162: 17
Current modulation level of boiler.
You can set the modulation level to measure the flue gas if
P 163 flue gas measurement is active.
yes
17
P163
Flue gas measure
P163: 0
If flue gas measurement is active, the modulation level of the
boiler is switched off. This can be set in P162. This remains
fixed for the duration of the activation.
0 = inactive
1 = active – minimum power
17= maximum power.
Note:
After 20 minutes has expired, (P164) the flue gas
measurement finishes automatically.
yes
0
P164
Flue gas meas ti
P105: 20m
Max. duration of flue gas measurement
Displayed only if P163=1
yes
20
P170
Burner start
P170: 0
Select between 2 types of burner control:
0: Pellet boiler runs inline with the burner demand signals
from the heating controller
1: Pellet boiler starts, if it receives a single pulse from the
heating controller and switches off when the switch-off
temperature is reached.
yes
0
P171
Malfunction output
P171: 0
When a malfunction occurs the boiler controller triggers the
malfunction relay. The potential-free contact (output SM 20
19) enables the alarms to be displayed using an external
malfunction system (230V). You can select the following
functions:
0:
The contact closes when a malfunction occurs – normally
open
1:
When a malfunction occurs the contact opens and closes
in flashing pulses.
1 pulse = all other malfunction
2 pulses = one of the sensors is defective
3 pulses = one of the motors is defective
4 impulses = safety temperature sensor Emergency OFF
2:
If a malfunction occurs the contact opens – normally closed
3:
When malfunction "Ash box full" occurs a flashing pulse is
signalled and all malfunction contacts closes
Note:
If a remote maintenance system is implemented then
an SMS text is transmitted for each flashing contact.
yes
0
P172
Flashing time
P172: 20s
Flashing time for warning "Ash!", parameter 171 must be
set to 3.
yes
20
P173
Flashing pulse
P173: 1
Flashing pulse for warning "Ash!", screen must indicate 3 for
the fault display.
yes
1
PE 3671 USA 2.3
Installation Manual PES 36–56
Содержание Pellematic PES 12-20
Страница 38: ...Connecting up to the power supply 38 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 46: ...Connecting up to the power supply 46 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 47: ...Connecting up to the power supply 47 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 52: ...Operating the pellet boiler 52 Setting date and time Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 88: ...Appendix 88 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 92: ...Appendix 92 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 99: ...Appendix 99 Labeling 105x74 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 100: ......