Starting up for the first time
64
P180
Function RES2
P180: 2
Output boiler controlled pump RES2 (230V): is used to
control a accumulator pump, etc.
1 = release the output when minimum boiler temperature is
exceeded (P281)
2 = release the output when minimum boiler temperature is
exceeded (P281) and burner is requested (burner runout
time approx. 30 minutes, P280, value adjustable
yes
2
P181
Power RES2
P181: 100%
Display power draw of boiler controlled pump during pulse
mode
no
P183
Runout time
P183: 6h
Remaining burner runout time(hours) after malfunction text
"ash box full" until total switch-off.
yes
6
P184
Ash auger speed
P184: 0 rpm
Displays speed of de-ashing auger
no
P185
Run time suction
P185: 80m
Run time (minuts) of burner auger until next suction interval
no
P186
Suction time total
P186: 68h
Operating hours of suction turbine, only on vacuum systems.
no
P187
Frequ RA vacuum
P187: 60s
Frequency for storage room suction systems in pulse mode,
only for vacuum systems - only if parameter 188 < 0
yes
60
P188
Pause RA vacuum
P188: 0s
Pause time for storage room extractor motor - suction system
in pulse mode. If pause time = 0 then no pulse mode.
yes
0
P189
Cleaning hour 1
P189: -1h
In parameter 190 you can set an additional boiler cleaning
time. The value to be set is the time (full hour) at which the
boiler cleaning sequence is to be performed.
Example: 10h = additional boiler cleaning at 10:00.
–1h = no additional cleaning sequence will be performed.
yes
-1
P190
Cleaning hours 2
P190: 20h
The value to be set is the time (full hour) at which the boiler
cleaning sequence is to be performed.
Example: 20h = additional boiler cleaning sequence to be
performed at 20:00.
Note:
On vacuum systems the hopper is also filled at the
same time,
regardless of whether it is empty or not.
yes
20
P191
Min run time RM
P191: 12h
Minimum running time (hours) of boiler until next cleaning
sequence.
yes
12
P192
Cleaning duration
P192: 120s
Duration of the boiler cleaning sequence in seconds.
yes
120
P193
Min run time
scrubbing
P193: 6h
Minimum running time (hours) of boiler until next cleaning of
heat exchanger -
only on condensing boilers
.
6
P194
Scrubbing duration
P194: 45s
Duration of scrubbing low temperature heat exchanger -
only
on condensing boilers.
45
P195
Min run time ash
P195: 120min
Minimum running time of boiler until next de-ashing
procedure, value adjustable - parameter available only when
external de-ashing system is connected.
yes
120/80/45
P196
Ash duration
P196: 3min
Duration of running time (minuts) of ash auger, value
adjustable, parameter for external de-ashing system only.
yes
3/3/5
Installation Manual PES 36–56
PE 3671 USA 2.3
Содержание Pellematic PES 12-20
Страница 38: ...Connecting up to the power supply 38 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 46: ...Connecting up to the power supply 46 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 47: ...Connecting up to the power supply 47 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 52: ...Operating the pellet boiler 52 Setting date and time Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 88: ...Appendix 88 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 92: ...Appendix 92 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 99: ...Appendix 99 Labeling 105x74 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 100: ......