Starting up for the first time
58
12.3 Output test
The output test is designed to test all outputs connected to the system (e.g. all motors, the alarm signal relay, the
solenoid valve and the recirculation pump).
Parameter level 200
Open the menu
Pellematic
at the operating device. Parameter level 200 is exclusively for customer service technicians
and MEco employees. You access parameter level 200 by entering the code in parameter P199. The code for parameter
level 200 is the sum of day plus hour, e.g. : Day:
26
/ 08/ 2009 and hour:
14
:30:47; (26 + 14 = 40) results in the code: 26
+ 14 = 40
Then go to parameter 203 to test all outputs.
Para-
meter
Display on screen
Description
Adjus
table
Factory
setting
P203
Output test
P203: Enter
Output test - using the thumbwheel you can select each
individual output. Press Enter to switch the output on. The
current power draw is shown for motors. Press Enter again
to switch the output off. The outputs for the suction fan
and the air blower can be increased by 20% each time
the button is pressed. Once you have reached 100%, the
next press of the button returns the setting to 0%. Exit the
output test menu at the bottom of the list.
yes
Outputs/motors
Designation
Check if
If not, then check if
Burner motor
ES
the motor that feeds pellets to the burner
is running
• the burner motor is connected
• the burner motor rotates easily
• the motor is defective
Suction turb
ZW
the suction turbine at the hopper is running
• the suction turbine is connected
• the fuse is defective
• the motor is defective
Fuel tr sys M
RA
the fuel transport system – motor is running
• the fuel transport system motor is connected
• the fuel transport system motor rotates easily
• the fuel transport system motor is defective
De-ashing motor
AV (optional for PE
12–32)
the motor de–ashing system is running
• the de–ashing system is switched on (P212)
• the de–ashing system is properly located and
locked in position
• the de–ashing system is correctly wired up
Burner plate
de-ashing motor
AV (optional for PE
12–32)
the burner plate de-ashing motor is running
• the burner plate de-ashing system is switched
on (P212)
• the burner plate de-ashing system is properly
located and locked in position
• the burner plate de-ashing system is correctly
wired up
Burner fan
LUFT
the burner fan is running
Note:
You can set 5 power levels:
20/40/60/80/100)
• the wiring is correct
• the motor is defective
Installation Manual PES 36–56
PE 3671 USA 2.3
Содержание Pellematic PES 12-20
Страница 38: ...Connecting up to the power supply 38 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 46: ...Connecting up to the power supply 46 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 47: ...Connecting up to the power supply 47 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 52: ...Operating the pellet boiler 52 Setting date and time Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 88: ...Appendix 88 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 92: ...Appendix 92 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 99: ...Appendix 99 Labeling 105x74 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 100: ......