Starting up for the first time
62
P119
Current flue gas
P119: 30%
Flue gas fan power in percent.
no
P120
Current ignition
P120: 128s
Current ignition time
This is 0 if the ignition is not active.
no
P124
Comb ch setpoint
P124: 1472°F
Combustion chamber setpoint
Displayed on while combustion chamber temperature control
is active and the combustion chamber sensor is connected.
no
P125
Negative draft
P125: 60EH
Displays negative draft in the combustion chamber.
no
P126
Analog input 2
P126: 45%
not implemented
no
P130
AGT ign/comb.
P130: 212°F
Minimum flue gas temperature as condition for ignition and
combustion chamber control.
Displayed only with flue gas sensor connected.
no
P131
Flue gas min.
P131: 212°F
The minimum flue gas temperature for the boiler controller.
If the temperature falls below the minimum flue gas
temperature, the boiler increases the power independently of
the boiler temperature. Displayed only with flue gas sensor
connected
yes
100
P132
Current weight
P132: 74kg
Displayed only, if P233 is 1.
Display of the current weight in the FleXILO textile tank.
P133
Current weight
P133: 74kg
Displayed only, if P233 is 2.
Display of the current weight in the storage room.
P134
Low weight lim
P134: 0kg
Displayed only, if P233 is 1 or 2.
The threshold value, the minimum weight for a warning
message, can be varied. The warning message appears on
the operating device and disappears when the filling weight
is above the set minimum weight.
P135
Weight hopper
P135: 0kg
Displayed only, if P233 is 2.
Display of the current weight in the hopper.
P136
Pellet level
P136: 0
Displayed only, if P233 is 3.
Display of the pellet level
1 = full
0 = empty – warning message displayed on the operating
device.
P137
Refill capacity
P137: 0kg
Displayed only, if P233 is 3.
Set the filling capacity after refilling the storage
P138
Save capacity
P138: 0
Displayed only, if P233 is 3.
Save the set filling capacity. By turning to 1 the filling capacity
is added to the actual weight and P137 is reset to 0
P152
Motors
P152: Enter
Pressing ENTER takes you to the motors sub-menu. Select
a motor using the thumbwheel. The following data are
displayed for each motor connected: mA-actual, Volt-actual,
mA-minimum-setpoint, mA-maximum-setpoint, operating
hours, time duration that the motor may operate outside the
Min-Max values before an alarm is triggered. The Min-Max
values and time duration are adjustable.
ja
Installation Manual PES 36–56
PE 3671 USA 2.3
Содержание Pellematic PES 12-20
Страница 38: ...Connecting up to the power supply 38 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 46: ...Connecting up to the power supply 46 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 47: ...Connecting up to the power supply 47 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 52: ...Operating the pellet boiler 52 Setting date and time Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 88: ...Appendix 88 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 92: ...Appendix 92 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 99: ...Appendix 99 Labeling 105x74 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 100: ......