Starting up for the first time
66
12.5 Parameter level 200
Parameter level 200 is exclusively for customer service technicians and MEco employees. You access parameter level
200 by entering the code in parameter P199. The code for parameter level 200 is the sum of day plus hour, e.g. : Day:
26
/ 08/ 2009 and hour:
14
:30:47; (26 + 14 = 40) results in the code: 26 + 14 =
40
You can use this parameter to adjust the function of the pellet heating system. Parameter level 200 has 99 values, from
200 – 299. Not all parameters are implemented. Parameters that are not used are also not displayed on the operating
device.
There are adjustable parameters and non-adjustable parameters. Press Enter to switch adjustable parameters to edit
mode.
Note:
The control system automatically switches back to the standard display if you do not make any entries for 30
minutes. After a further 30 minutes the backlight on the screen switches off.
Changing a parameter
1.
Select a parameter using the thumbwheel.
2.
Press Enter
3.
►Parameter appears in brackets◄
4.
Change the value of the parameter using the thumb wheel
5.
Confirm by pressing Enter
Note:
Pressing Enter has no effect on non-adjustable parameters.
Description of parameter
Para-
meter
Display on screen
Description
Adjus
table
Factory
setting
P200
Level 1
P200: Enter
Press Enter to access level 1
no
P202
Switch-off temp
P202: 185°F
The boiler switches off when it reaches the switch-off
temperature
yes
185
P203
Output test
P203: Enter
Output test - using the thumbwheel you can select each
individual output. Press Enter to switch the output on.
The current power draw is shown for motors. Press again
to switch the output off. The outputs for the flue gas fan
and the air blower can be increased by 20% each time
the button is pressed. Once you have reached 100%, the
next press of the button returns the setting to 0%. Exit the
output test menu at the bottom of the list.
yes
P204
Malfunctions
P204: Enter
Page through the malfunction fault text archive using the
thumbwheel. When the alarm text archive is full, the next
alarm text overwrites the oldest alarm text.
Press Enter to return to the parameter level
no
P205
Maintenance month
P205: 0
Month in which the display indicates maintenance to
performed on boiler
0 – maintenance text deactivated
yes
0
P206
Maintenance day
P206: 0
Day on which the maintenance message is displayed on
the boiler.
0 – maintenance text deactivated
yes
0
P207
Flue gas temp Max
P207: 238°F
Displays the highest flue gas temperature recorded so far;
can be reset to 0.
yes
Installation Manual PES 36–56
PE 3671 USA 2.3
Содержание Pellematic PES 12-20
Страница 38: ...Connecting up to the power supply 38 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 46: ...Connecting up to the power supply 46 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 47: ...Connecting up to the power supply 47 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 52: ...Operating the pellet boiler 52 Setting date and time Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 88: ...Appendix 88 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 92: ...Appendix 92 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 99: ...Appendix 99 Labeling 105x74 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 100: ......