Starting up for the first time
71
P273
Reset time SZ
P273: 10s
I proportion for negative draft control in combustion
chamber temperature (displays only with connected
negative draft controller)
yes
10
P274
Derivative SZ
P274: 2 zs
D proportion for negative draft control in combustion
chamber temperature (displays only with connected
negative draft controller)
yes
2
P280
Run on RES2
P280: 15m
Run on time for boiler controlled pump after burner
switches off - in minutes
yes
15
P281
Boiler min. temp.
P281: 140°F
Switch-on temperature from boiler-controlled pump output
yes
140
P282
Boiler min. hyst.
P281: 5°F
Hysterisis for boiler minimum temperature
yes
5
P283
Control range RES2
P283: 9°F
Control range of output from boiler-controlled pump. The
control range starts at the minimum boiler temperature
with a speed of 30% and increases to the boiler minimum
tempe control range to 100% speed.
yes
9
P284
Min speed AV
P284: 2
Is the minimum speed of the ash auger in rounds per
minute. If the ash auger turns less than 2 rounds per
minute, the warning message appears on the operating
device.
yes
2
P285
Suction int. setpoint
P295: 175
Burner run time in minutes until filling hopper.
no
175/200/100
P293
Pellematic
P293: 1
Boiler code for cascade connection. It only changes when
2, 3 or 4 Pellematic plugs are plugged in for a cascade
system of pellet boilers.
no
1
P294
Hand filling hopper
P294: 0
Set whether pellet boiler is installed as boiler with hand
filling hopper.
0 = inactive, 1 = active
Note:
This parameter is only shown with auger delivery
system.
yes
0
P295
Delete alarm
P295: 0
You can delete the alarm archive (P204).
Note:
Parameter is automatically reset to 0
yes
0
P296
Motor code
P296: 0
A motor remains active until the motor detection starts
again. If a motor is connected incorrectly, you can
deactivate it again.
Note:
Parameter is automatically reset to 0
yes
0
P297
CF card format
P297: 0
Format a Compact Flash card. Press Enter to select edit
mode. Use menu scroll to set value 1. The formatting
process starts. After a short time (1 second) value 1 returns
to 0. Formatting finishes. The format process deletes
everything on the CF card.
yes
0
P298
Standard param
P298: 0
Load standard parameters (default values). Use the menu
scroll to set the value to 1. The standard parameters are
loaded. After a short time (1 second) value 1 returns to 0.
The parameter loading process finishes. All parameters in
levels 100, 200 and 300 are now set to the factory settings.
yes
0
P299
Level 3 passw.
P299: 0
Access level 3 - level for MEco technical department, enter
password
no
PE 3671 USA 2.3
Installation Manual PES 36–56
Содержание Pellematic PES 12-20
Страница 38: ...Connecting up to the power supply 38 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 46: ...Connecting up to the power supply 46 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 47: ...Connecting up to the power supply 47 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 52: ...Operating the pellet boiler 52 Setting date and time Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 88: ...Appendix 88 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 92: ...Appendix 92 Installation Manual PES 36 56 PE 3671 USA 2 3...
Страница 99: ...Appendix 99 Labeling 105x74 PE 3671 USA 2 3 Installation Manual PES 36 56...
Страница 100: ......